Vibration Design of mass timber structures

Mass Timber has emerged as a leading sustainable construction material, attracting strong interest from developers, architects, engineers, and policymakers. However, concerns around floor vibration performance continue to present challenges to its broader adoption. The McNamara Salvia Vibrations Group has conducted in-situ testing of constructed mass timber floor systems to better understand their dynamic response to footfall excitation. These results are used to calibrate and refine our advanced vibration models, enhancing the accuracy of our analyses. By combining field data with sophisticated modeling and simulation, we design optimized mass timber floor systems that achieve the required vibration performance criteria while maintaining the benefits of this innovative material.

vibration testing

cross-laminated timber floor

Project Highlights 

We conducted a set of vibration tests on a residential building floor with cross-laminated timber (CLT) panels to understand the effect of non-structural components on the dynamic response of the floor. The floor construction included a single 7-ply CLT panel in a three-span configuration, with a maximum span of 27.75 ft, finished with an acoustical mat and a 1.5-inch-thick gypcrete topping.

vibration criteria

The floor structure was designed to meet the vibration criteria for residences (16,000 to 32,000 mips – micro-inches per second) per U.S. Mass Timber Floor Vibration Design Guide. 

Solution Strategy 

Vibration tests were conducted as the building construction is nearing its completion at two separate times. For Test 1, all CLT panels and the studs of the partition walls were installed. For Test 2, gypcrete topping and the acoustical mat on the CLT panels, as well as the gypsum boards of the partition walls, were all installed.
The following tests were conducted:

  1. Heel drop tests
  2. Walking tests
  3. Instrumented impact hammer tests

 

results 

Analysis of the vibration data showed that adding non-structural components increased the floor’s fundamental frequency by about 20% and reduced walking-induced vibrations by roughly 47% on average. The stiffness of completed partition walls also altered the fundamental mode shape, an effect not observed when only wall studs were present. Finite element models of the tested structures were also developed by our team to identify parameters that would more accurately capture the effect of non-structural components. 

Before and after Test